Pipe Freezing
.
Save Water...Save
Time... Save Money... Stay Green!
.
Tap Master's proven effective method of
Pipe freezing isolates your piping when draining the system is not
economical or environmentally sound. Valve additions and repairs are
made quick and easy. Great for high pressure and copper systems.
less draining allows you to stay in the green. |
.
|
|
Tap Master
Inc.'s
proven effective method of Line Freezing isolates your
pipeline when draining the system is not economical or
environmentally sound. Valve additions and repairs are made quick
and easy. Great for high pressure and copper systems |
|
|
|
 |
|
The two 4" pipe freezes were needed
for relocation of the
piping, due to new duct work at the
hospital renovation. |
|
|
|
 |
|
Once completed the two 4" lines were
rerouted without the need for valves |
|
|
|
 |
|
Because the pipe was using VIC
couplings no welding was
needed, the pipe was roll grooved with
a portable groover.
This allowed the pipe to be cut within
inches of the freeze. |
|
|
|
 |
|
8" pipe freeze isolation on steel
chilled water supply line at the
UCLA power plant. Note; the pipe
freeze location from the main.
Because the chilled water is 48° F,
it's affect on the freeze is
minimal. If this were a hot water
line, the distance from the main
would be significantly greater due to
the elevated temperature. |
|
|
|
 |
|
The two 8" Pipe Freeze isolations at
Doctors Medical Center,
Modesto are isolating a chilled water
supply and return line at
the same time. Valves were installed
near the pumps to allow
for future servicing. |
|
|
|
 |
|
Verification of a successful pipe
freeze can be seen in the frost
line at each end of the pipe freeze
jacket, as well as the
temperature monitor readings of the
pipe sensors 2" from the end
of each freeze. Time tables are used
as a guide only as there are
to many variables to predict exact
freeze times in the field. |
|
|